FN7-12DR Model indoor AC HV Load Switch is suitable in 50Hz,rated voltage of 12Kv the three-phase AC power system
as the breaking load short-circuit current of the power and used the Closing,
until the combination of electrical short -circuit current can be breaking any current
can be used as protection purposes .
FN7-12DR Indoor High Voltage Load Break Switch
Summary
FN7-12DR Model indoor AC HV Load Switch is suitable in 50Hz,rated voltage of 12Kv the three-phase AC power system as the breaking load short-circuit current of the power and used the Closing, until the combination of electrical short -circuit current can be breaking any current can be used as protection purposes .
Specifications
Rated voltage(KV) | 12 | ||||
Insulation level | 1min frequency voltage(KV) | Phase to phase earth42 | Isolation fracture48 | ||
Lightning impulse withstand voltage(KV) |
Phase to phase earth75 | Isolation fracture85 | |||
Rated current(A) | 400 | 630 | |||
4S Rated thermal current(KA) | 12.5 | 20 | |||
Rated active load breaking currentKA(Peak) | 31.5 | 50 | |||
Rated short circuit making current(KA peak) | 31.5 | 50 |
Name | Models | DS | DX | L | R | RA | F | USE | |
Grounding switch incoming fedder side |
Grounding switch outgoing fedder side |
Interlock device |
Fuse | Impact Fuse | Electric sub- gate devices |
||||
Load switches |
Non-impact fuse |
FN7-12 | — | — | — | — | — | — | Line load switch |
FN7-12DSL | △ | — | △ | — | — | — | |||
FN7-12DXL | — | △ | △ | — | — | — | |||
FN7-12R | — | — | — | △ | — | — | Transformer Protection |
||
FN7-12DSLR | △ | — | △ | △ | — | — | |||
FN7-12DXLR | — | △ | — | △ | — | — | |||
With impact fuse |
FN7-12RAF | — | — | — | — | △ | △ | Transformer Protection |
|
FN7-12SLRAF | △ | — | △ | — | △ | △ | |||
FN7-12XLRAF | — | △ | △ | — | △ | △ |