ZW32-24 outdoor HV vacuum circuit breaker

Notes

1.Installation way: pole mounted;
2.Operating mechanism: spring operating mechanism and permanent magnetic operating mechanism;
3.Pole type: integrated pole;
4.Application: outdoor 24kV substation, power plant.
5.Operation type: manual, electric, remote control.

Detailed introduction

ZW32-24 outdoor HV vacuum circuit breaker

ZW32-24 Outdoor High Voltage Vacuum Circuit Breaker

Summary
ZW32-24 outdaoor HV vacuum circuit breaker is a 3-phase AC 50Hz 24kV outdoor switch equipment.
1.Installation way: pole mounted;
2.Operating mechanism: spring operating mechanism and permanent magnetic operating mechanism;
3.Pole type: integrated pole;
4.Application: outdoor 24kV substation, power plant.
5.Operation type: manual, electric, remote control.

※ Product Standards
1.IEC62271-100 High Voltage Switchgear and Controlgear Part 100: AC Circuit-breakers
2.GB1984 High Voltage AC Circuit-breakers
3.GB/T11022 Common Specifications for High-voltage Switchgear and Controlgear Standards
4.JB/T 3855 High Voltage AC Vacuum Circuit-breakers
5.DL/T402 Specification of High-voltage AC Circuit-breakers
 
※ Environmental Conditions
1.Ambient temperature: -35°C ~ +40°C;
2.Altitude: ≤2000m;
3.Wind speed ≤ 35m/s;
4.Earthquake intensity: ≤8 level;
5.Filthy level: IV;
6.Installation places: No fire, explosion hazard or serious filthy.

Technical Specifications

No. Item Units Parameters
1 Rated voltage Kv 24
2 Rated frequency Hz 50
3 Rated current A 630 1250
4 Rated short-circuit breaking current kA 20 25
5 Rated peak withstand current(peak) kA 50 63
6 Rated short-circuit closing current(peak) kA 40 63
7 Rated short-time withstand current and duration kA/S 20/4 25/4
8 Rated operation sequence   O-0 . 3s-CO-180s-CO
9 Mechanical life Times 10000
10 Breaking times of  rated short-circuit breaking current Times 20
11 1min power frequency withstand voltage (wet) over the groundlinter phase/fracture kV 50/65
(dry) over the groundlinter phaseffracture 65/79
Secondary loop 3
12 Lighting impulse withstand voltage(peak)  Overthe group,interphase/fracture KA 125/145

Model Implication


Overall Dimensions

Message Feedback

If you have any enquiry about quotation or cooperation,please free to email us at niki@zhiyue.com or use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.

News Center

Vacuum Circuit Breaker Technology and Application: The Key to Enhancing Power System Reliability

Power Capacitor as the Key Power in the Electric Power System

What are the main performance characteristics of vacuum contactors?

What is the purpose of power capacitors?

Can't find what you're looking for?
In the past 32 years, Zhiyue Group Co., Ltd. has been helping many well-known companies and organizations to provide high-voltage power capacitors, low-voltage capacitors, vacuum contactors, vacuum circuit breakers, high-voltage load switches, high-voltage disconnect switch, high voltage transformer.
Contact Our Experts
Message
Cell Phones Telephone E-mail

Back To Top

Leave Message Here!
GET IN TOUCH NOW
×
We value your privacy
We use cookies to provide you with a better online experience, analyse and measure website usage, and assist in our marketing efforts.
Accept All