CKSC Dry-type iron-core reactor

CKSC Dry-type iron-core reactor
Notes

1. the frequency of system
2. rated current
3. Rated reactance rates.
4. rated capacity
5. the style of installation(horizontal/ overstow)

Detailed introduction

Dry-type iron-core reactor

CKSC Dry-type iron-core reactor

General Description:
1,CKSC Dry-type iron-core reactor uses the contracture of dry-type air-core. The iron-core uses silicon steel, iron-core columns are made by the number of air gap evenly. Air gap uses epoxy glass cloth board as a filler, to ensure that the gap does not change in the long-running.
2,Dry-Core Reactor has the quality of simple structure, small size, light weight, reasonable layout, easy installation, and is the ideal equipment used in capacitance compensation framework indoors and cabinet device without electromagnetic pollution, without oil pollution, just with good flame retardant.
3,It has the quality of excellent thermal performance, good insulation, high mechanical strength, good dynamic and thermal stability, without cracking occurrence.
4,The tap between core columns and Insulation cylinder is fixed by epoxide-resin glue and is tensioned by Pull screw pole to make the coil and iron-core combined into one, to strengthen insulation strength of the core and coil, which greatly reduced the running noise of the reactor.
5,Coil and core, core and ground are added special insulation components, to ensure the electrical insulation distance.
6, The use of special computer software assisted optimization design, accurate inductance value, and the temperature rise to leave a reasonable margin to ensure that the reactor core temperature less than 75K, coil temperature rise not more than 65K, at the same time to ensure the dry-core reactor1.35 times the rated power frequency current long-term run.

Working condition:
1,Application Environment: Outdoors, indoors
2,The temperature of environment: -40°C-+45°C(according to the demand of user)
3,The latitude: (According to the demand of user)
4,The place of installation and running: Without severe vibration, can endure the 8 earthquake
5,The place of installation: without Harmful gases, stream, the Conductive and explosive ass
6,Maintain ventilation used indoors
7,The maximum wind speed: not more than
8,The compare moisture: no more than 90% of month average and no more than 95% of the daily average.

The parameter of system:
1. the frequency of system
2. rated current
3. Rated reactance rates.
4. rated capacity
5. the style of installation(horizontal/ overstow)
6. the usage environment(indoors/outdoors)
7. the angle of outlet and into
8. the special demand of orderThe characteristics of product:

For the specification of CKSC type, 10kv system, three phase, the reactance ratio is 1%

Model Capacitor output(kVAr) Capacitor voltage (kV) Reactor output(kVAr) Inductance(mH) Rated current (A)
CKSC-1/10-1% 100 11√3 1 3*38.52 5.25
CKSC-2/10-1% 200 11√3 2 3*19.26 10.5
CKSC-3/10-1% 300 11√3 3 3*12.84 15.75
CKSC-4.5/10-1% 450 11√3 4.5 3*8.569 23.62
CKSC-6/10-1% 600 11√3 6 3*6.420 31.49
CKSC-7.5/10-1% 750 11√3 7.5 3*5.133 39.37
CKSC-9/10-1% 900 11√3 9 3*4.285 47.24
CKSC-10/10-1% 1000 11√3 10 3*3.852 52.49
CKSC-12/10-1% 1200 11√3 12 3*3.210 62.97
CKSC-15/10-1% 1500 11√3 15 3*2.570 78.73
CKSC-18/10-1% 1800 11√3 18 3*2.140 94.48
CKSC-21/10-1% 2100 11√3 21 3*1.926 110.22
CKSC-24/10-1% 2400 11√3 24 3*1.65 125.97
CKSC-27/10-1% 2700 11√3 27 3*1.427 141.72
CKSC-30/10-1% 3000 11√3 30 3*1.284 157.46

For the specification of CKSC type, 10kv system, three phase, the reactance ratio is 6%

Model Capacitor output(kVAr) Capacitor voltage (kV) Reactor output(kVAr) Inductance(mH) Rated current (A)
CKSC-6/10-6% 100 11√3 6 3*233.223 5.25
CKSC-9/10-6% 150 11√3 9 3*153.514 7.87
CKSC-12/10-6% 200 11√3 12 3*115.501 10.5
CKSC-18/10-6% 300 11√3 18 3*77.246 15.75
CKSC-27/10-6% 450 11√3 27 3*3*51.388 23.62
CKSC-30/10-6% 500 11√3 30 3*46.289 26.24
CKSC-36/10-6% 600 11√3 36 3*38.500 31.49
CKSC-45/10-6% 750 11√3 45 3*30.781 39.37
CKSC-54/10-6% 900 11√3 54 3*25.694 47.24
CKSC-60/10-6% 1000 11√3 60 3*23.100 52.49
CKSC-72/10-6% 1200 11√3 72 3*19.250 62.97
CKSC-90/10-6% 1500 11√3 90 3*15.410 78.73
CKSC-108/10-6% 1800 11√3 108 3*12.833 94.48
CKSC-126/10-6% 2100 11√3 126 3*11.005 110.22
CKSC-144/10-6% 2400 11√3 144 3*9.625 125.97
CKSC-162/10-6% 2700 11√3 162 3*8.559 141.72
CKSC-180/10-6% 3000 11√3 180 3*7.700 157.46
CKSC-198/10-6% 3300 11√3 198 3*7.002 173.21
CKSC-216/10-6% 3600 11√3 216 6*6.420 188.96
CKSC-240/10-6% 4000 11√3 240 3*5.778 209.95
CKSC-252/10-6% 4200 11√3 252 3*5.503 220.45
CKSC-288/10-6% 4800 11√3 288 3*4.814 251.94
CKSC-300/10-6% 5000 11√3 300 3*4.622 262.44
CKSC-360/10-6% 6000 11√3 360 3*3.851 314.93
CKSC-480/10-6% 8000 11√3 480 3*2.888 419.9

For the specification of CKSC type, 10kv system, three phase, the reactance ratio is 12%

Model Capacitor output(kVAr) Capacitor voltage (kV) Reactor output(kVAr) Inductance(mH) Rated current (A)
CKSC-12/10-12% 100 12√3 12 3*551.074 5.25
CKSC-18/10-12% 150 12√3 18 3*367.383 7.87
CKSC-18/10-12% 200 12√3 24 3*275.537 10.5
CKSC-18/10-12% 300 12√3 36 3*183.691 15.75
CKSC-18/10-12% 450 12√3 54 3*121.897 23.62
CKSC-18/10-12% 1000 12√3 120 3*54.993 52.49
CKSC-18/10-12% 1200 12√3 144 3*45.843 62.97
CKSC-18/10-12% 1500 12√3 180 3*36.637 78.73
CKSC-18/10-12% 1800 12√3 216 3*30.545 94.48
CKSC-18/10-12% 2100 12√3 252 3*26.190 110.22
CKSC-18/10-12% 2400 12√3 288 3*22.902 115.97
CKSC-18/10-12% 2700 12√3 324 3*20.363 141.72
CKSC-18/10-12% 3000 12√3 360 3*18.331 157.46
CKSC-18/10-12% 3300 12√3 396 3*16.657 173.21
CKSC-18/10-12% 3600 12√3 432 3*15.272 188.96
CKSC-18/10-12% 4000 12√3 480 3*13.748 209.95
CKSC-18/10-12% 4200 12√3 504 3*13.088 220.45
CKSC-18/10-12% 4800 12√3 576 3*11.456 251.94
CKSC-18/10-12% 5000 12√3 600 3*10.994 262.44
Message Feedback

If you have any enquiry about quotation or cooperation,please free to email us at niki@zhiyue.com or use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.

News Center

Vacuum Circuit Breaker Technology and Application: The Key to Enhancing Power System Reliability

Power Capacitor as the Key Power in the Electric Power System

What are the main performance characteristics of vacuum contactors?

What is the purpose of power capacitors?

Can't find what you're looking for?
In the past 32 years, Zhiyue Group Co., Ltd. has been helping many well-known companies and organizations to provide high-voltage power capacitors, low-voltage capacitors, vacuum contactors, vacuum circuit breakers, high-voltage load switches, high-voltage disconnect switch, high voltage transformer.
Contact Our Experts
Message
Cell Phones Telephone E-mail

Back To Top

Leave Message Here!
GET IN TOUCH NOW
×
We value your privacy
We use cookies to provide you with a better online experience, analyse and measure website usage, and assist in our marketing efforts.
Accept All