Rated working voltage (Ue):1140V
Rated working current (Ie):800A, 1000,A1250A
Rated frequency (fr):50A
Name |
Unit |
Value |
|||
Main circuit |
Rated working voltage (Ue) |
V |
1140 |
||
Rated working current (Ie) |
A |
800, 1000,1250 |
|||
Rated frequency (fr) |
A |
50 |
|||
Rated making capacity |
A |
4Ie(AC-2) |
|||
Rated breaking capacity |
kV |
4Ie(AC-2) |
|||
Power frequency withstand voltage |
Between phases, phase to earth |
kV |
4.2 |
||
Vacuum breaks |
10 |
||||
Lightening impulse withstand voltage |
|
8 |
|||
Control circuit |
Rated voltage (Us) |
V |
AC. 220/380 |
||
Rated power (Ps) |
Electric holding |
VA |
≤1000/100 (absorbing/holding) |
||
Mechanical holding |
≤900/600 (closing/opening) |
||||
Auxiliary circuit |
Form |
|
3a+3b |
||
Rated value |
|
AC380V/5A, DC380V/1A |
|||
Control circuit, auxiliary circuit to earth power frequency withstand voltage |
kV |
2 |
|||
Rated operating frequency |
Long-term or mechanical holding type |
Time/h |
300 |
||
Short-term |
600 |
||||
Mechanical endurance² |
10000 times |
30 |
|||
Electrical endurance |
10000 times |
10 |
|||
Mechanical characteristics |
Closing time |
ms |
≤200 |
||
Original opening time |
ms |
≤160(electric holding) ≤60(mechanical holding) |
|||
3-phase synchronism |
ms |
≤3 |
|||
Closing tripping |
ms |
≤10 |
|||
Net weight |
kg |
31 |
If you have any enquiry about quotation or cooperation,please free to email us at niki@zhiyue.com or use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.