Name:Main circuit,Rated working voltage (Ue),Unit:kV,Value:7.2/12;
Name:Main circuit,Rated working current (Ie)Unit:A,Value:400,630;
Name:Main circuit,Rated frequency (fr),Unit:Hz,Value:50
Name |
Unit |
Value |
|||
Main circuit |
Rated working voltage (Ue) |
kV |
7.2 |
12 |
|
Rated working current (Ie) |
A |
400,630 |
|||
Rated frequency (fr) |
Hz |
50 |
|||
Rated making capacity |
A |
10Ie (AC-4) |
|||
Rated breaking capacity |
A |
8Ie (AC-4) |
|||
Rated short time withstand current |
A |
10Ie |
|||
Rated peak withstand current |
A |
25Ie |
|||
Rated short circuit duration |
s |
4 |
|||
Power frequency withstand voltage |
Incoming wiring terminal to earth |
kV |
42 |
||
Outgoing wiring terminal to earth* |
kV |
42 |
|||
Vacuum breaks |
kV |
42 |
|||
Lightening impulse withstand voltage |
kV |
75 |
|||
Control circuit |
Rated voltage (Us) |
V |
AC or DC. 110/220 |
||
Rated power (Ps) electric holding |
VA |
≤1000/100 (absorbing/holding) |
|||
Auxiliary circuit |
Form |
|
3a+3b |
||
Rated value |
|
AC 380V/5A, DC 380V/1A |
|||
Control circuit, auxiliary circuit to earth power frequency withstand voltage |
kV |
2 |
|||
Rated operating frequency |
Long-term |
time/h |
300 |
||
Short-term |
time/h |
600 |
|||
Mechanical endurance |
10000 times |
30 |
|||
Electrical endurance |
10000 times |
10 |
|||
Mechanical characteristics |
Closing time |
ms |
≤200 |
||
Original opening time |
ms |
≤120 |
|||
Closing tripping |
ms |
≤10 |
|||
Net weight |
kg |
15.2 |
16.3 |
||
Remark: * item only applies to heightening type. |
If you have any enquiry about quotation or cooperation,please free to email us at niki@zhiyue.com or use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.