JCZ5-12KV Vacuum Contactor

Notes

。High-voltage AC vaccum contactor
。Designed code
。Rated voltage(kV)
。Latching mode:J—machanical latch; D—electrical latch
。G—high altitude; Y—movable type; None—basic type

Detailed introduction

JCZ5-12KV Vacuum Contactor

General Description:
VCZ5-7.2,12/400,630 series vacuumcontactor is used in an AC. 50-60 Hz electric power system, with rated working voltage is 7.2Kv and 12kV, and rated current of 400A,630A, for direct or romote on-off control and circuit-breaking control of the of the main load. It is especially suitable for the frequently operated electric control applications such as electric motors, transformer, etc. This series adopts integrated framework, before-and-after layout between the main circuit and controlling circuit, adopts electrical latch or machanical latch, and vacuum interrupter with ceramic shell.

Main Specifications:
1. High-voltage AC vaccum contactor
2. Designed code
3. Rated voltage(kV)
4. Latching mode:J—machanical latch; D—electrical latch
5. G—high altitude; Y—movable type; None—basic type
6. Rated current(A)
7. Rated short-time withstand current(kA)
8. Vaccum shell materials: T—ceramic

Technical Data:

NO.

Parameters

Unit

Value

JCZ5-7.5J/D-630/400/250

JCZ5-12J/D-630/400/250

1

Rated Voltage

kV

7.2

12

2

Rated Current

A

630

400

250

630

400

250

3

Rated closing current (rms)

A

6300

4000

2500

6300

4000

2500

4

rated breaking current

5040

3200

2500

5040

3200

2500

5

4S thermal current

6300

4000

2500

6300

4000

2500

6

Limit breaking current

6300

4000

2500

6300

4000

2500

7

Power frequency withstand voltage

kV

32

42

8

operating frequency

Times/h

300

9

Electric life time

AC-3

×104 Times

25

AC-4

10

10

Mechanical life

30

11

Rated operating voltage

V

AC110/220

12

Closing coil pull current

A

≤ DC6/3

13

Holding coil holding current

D:DC0.32/0.16

14

Shunt trip coil current

J:DC2.5/1.3

NO.

Parameters

Unit

Value

JCZ5-7.2J/D-630/400/250

JCZ5-12J/D-630/400/250

1

contact distance

mm

4.5+1.0/-0.5

6+1.0-0.5

2

contact overtravel

1.5±0.5

3

Average closing speed

m/s

0.1~0.25

4

Average opening speed

0.3~0.6

5

3 Phase closing - opening period                                  

ms

≤ 2

6

Closing time / opening time

≤ 150/ ≤ 150

7

Each phase conductive loop resistance(20oC)

Ω

≤ 250

Model

Rated voltage (V)

Rated current main circuit(A)

Main contact parameters

Power frequency coltage resistance V(effective value)

Main circuit

control circuit

Distance (mm)

Overtravel(mm)

Final pressure(N)

Mian circuit

Auxillary circuit

Control circuit

JCZ5-7.5D(J)/160

7200

100,220

160

4.5±0.5

1.5±0.5

>85N

32000

2500

2000

JCZ5-7.5D(J)/250

7200

100,220

250

4.5±0.5

1.5±0.5

>85N

32000

2500

2000

JCZ5-7.5D(J)/400

7200

100,220

400

4.5±0.5

1.5±0.5

>85N

32000

2500

2000

JCZ5-7.5D(J)/630

7200

100,220

630

4.5±0.5

1.5±0.5

>85N

32000

2500

2000

Message Feedback

If you have any enquiry about quotation or cooperation,please free to email us at niki@zhiyue.com or use the following enquiry form,Our sales representative will contact you within 24 hous.thank you for your interest in our products.

News Center

Power Capacitor as the Key Power in the Electric Power System

What are the main performance characteristics of vacuum contactors?

What is the purpose of power capacitors?

What is the difference between a vacuum circuit breaker and an ordinary circuit breaker?

Can't find what you're looking for?
In the past 32 years, Zhiyue Group Co., Ltd. has been helping many well-known companies and organizations to provide high-voltage power capacitors, low-voltage capacitors, vacuum contactors, vacuum circuit breakers, high-voltage load switches, high-voltage disconnect switch, high voltage transformer.
Contact Our Experts
Message
Cell Phones Telephone E-mail

Back To Top

Leave Message Here!
GET IN TOUCH NOW
×
We value your privacy
We use cookies to provide you with a better online experience, analyse and measure website usage, and assist in our marketing efforts.
Accept All